Air Conditioning High Severity · Safety Lockout

Kosner / Giatsu / Mundoclima / Johnson Error Code P0 / P4: Meaning, Multimeter Diagnosis & Fix

Fault code P0 / P4 on Kosner / Giatsu / Mundoclima / Johnson units (Splits and Ducted Kosner (Nova, Gold), Giatsu (Aroma 2, GIA), Mundoclima (MUPR-H) and Johnson (Everest, JDM)) indicates: Protection against overcurrent of the IPM module or start failure of the Inverter compressor (Error P0 or P4). The electronic control module triggers this diagnostic trouble code when sensor feedback or actuator response in the Air Conditioning subsystem falls outside factory tolerances.

1. Technical Specifications & Multimeter Values (Kosner / Giatsu / Mundoclima / Johnson P0 / P4)

Manufacturer / BrandKosner / Giatsu / Mundoclima / Johnson
Error CodeP0 / P4
System / CategoryAir Conditioning
Compatible ModelsSplits and Ducted Kosner (Nova, Gold), Giatsu (Aroma 2, GIA), Mundoclima (MUPR-H) and Johnson (Everest, JDM)
Severity LevelHigh Severity · Safety Lockout
Multimeter SpecsInverter U-V-W compressor winding resistance: 0.9 Ω to 2.2 Ω balanced

2. Guided Symptom Troubleshooting Matrix

🔎 Does the outdoor unit try to start the compressor by jerking or vibrating and turns off displaying P0 or P4 on the split?
✓ Scenario A: Yes (Confirmed)

The **IPM** power module that converts the current to three phase for the compressor has cut out due to excess amps or overtemperature: 1) Is the rear radiator of the outdoor unit clogged with poplar lint or exposed to the sun at 45°C without ventilation? 2) If it runs cold the second you try to boot, a pin on the IPM module has been desoldered or the white thermal paste under the aluminum heatsink has dried.

✕ Scenario B: No (Not Present)

Disconnect the 3-wire plug from the compressor (U-V-W) and measure resistance between them: the 3 pairs should give exactly the same Ohms (~1.2 Ω).

3. Step-by-Step Multimeter Testing Procedure (P0 / P4)

  1. Safety Power Isolation: Disconnect the Kosner / Giatsu / Mundoclima / Johnson unit from mains power (230V / 120V AC) and wait at least 3 minutes for PCB capacitors to discharge before opening panels.
  2. PCB & Harness Terminal Check: Inspect the connectors associated with fault P0 / P4 for moisture, scale buildup, loose pins, or heat discoloration.
  3. Digital Multimeter Verification: Unplug the suspect sensor or actuator and measure its resistance (Ω) or supply voltage against the nominal reference: Inverter U-V-W compressor winding resistance: 0.9 Ω to 2.2 Ω balanced.
  4. Reassembly & Cycle Validation: Once the out-of-spec component is cleaned or replaced, restore power and execute the reset sequence.

4. How to Reset & Clear Kosner / Giatsu / Mundoclima / Johnson Error P0 / P4

🔄 Kosner / Giatsu / Mundoclima / Johnson P0 / P4 Reset: Cut the power for 5 minutes, clean the external condenser with water without pressure and check the thermal paste of the IPM module.
🛠️ Compatible Replacement Parts & Tools
Need to replace the faulty component (Replacement Sensor / Part)?

Check OEM & aftermarket availability for Kosner Replacement Sensor / Part:

Want to use the interactive diagnostic wizard or electrical calculators for Kosner / Giatsu / Mundoclima / Johnson P0 / P4?
⚡ Open in Interactive Simulator →

5. Frequently Asked Questions: Kosner / Giatsu / Mundoclima / Johnson Error Code P0 / P4

What does Kosner / Giatsu / Mundoclima / Johnson error code P0 / P4 mean?

Kosner / Giatsu / Mundoclima / Johnson P0 / P4: Protection against overcurrent of the IPM module or start failure of the Inverter compressor (Error P0 or P4) (Splits and Ducted Kosner (Nova, Gold), Giatsu (Aroma 2, GIA), Mundoclima (MUPR-H) and Johnson (Everest, JDM)). Multimeter Specs: Inverter U-V-W compressor winding resistance: 0.9 Ω to 2.2 Ω balanced.

How do I reset Kosner / Giatsu / Mundoclima / Johnson fault code P0 / P4?

Cut the power for 5 minutes, clean the external condenser with water without pressure and check the thermal paste of the IPM module.

What multimeter values should I check for Kosner / Giatsu / Mundoclima / Johnson code P0 / P4?

Inverter U-V-W compressor winding resistance: 0.9 Ω to 2.2 Ω balanced