Dixell / Eliwell Error Code P2: Meaning, Multimeter Diagnosis & Fix
Fault code P2 on Dixell / Eliwell units (Termostatos Digitales Cold Storage Rooms, Botelleros and Mesas Frías (XR20CX, XR60CX, ID974)) indicates: Failure in the evaporator defrost end probe (Equivalent to E2 in Eliwell). The electronic control module triggers this diagnostic trouble code when sensor feedback or actuator response in the Commercial Refrigeration & Catering subsystem falls outside factory tolerances.
1. Technical Specifications & Multimeter Values (Dixell / Eliwell P2)
| Manufacturer / Brand | Dixell / Eliwell |
|---|---|
| Error Code | P2 |
| System / Category | Commercial Refrigeration & Catering |
| Compatible Models | Termostatos Digitales Cold Storage Rooms, Botelleros and Mesas Frías (XR20CX, XR60CX, ID974) |
| Severity Level | Medium Severity · Protection Mode |
| Multimeter Specs | NTC evaporator probe at 25°C: 10 kΩ (at -10°C: ~55 kΩ) |
2. Guided Symptom Troubleshooting Matrix
🔎 Does 'P2' appear alternating with the chamber temperature?
✓ Scenario A: Yes (Confirmed)
The second probe (the one punctured between the aluminum fins of the interior evaporator) is cut or out of range. The chamber continues to cool, but the defrosts will be done by fixed time instead of by temperature.
✕ Scenario B: No (Not Present)
Replace the evaporator probe connected to the 'Probe 2' input.
3. Step-by-Step Multimeter Testing Procedure (P2)
- Safety Power Isolation: Disconnect the Dixell / Eliwell unit from mains power (230V / 120V AC) and wait at least 3 minutes for PCB capacitors to discharge before opening panels.
- PCB & Harness Terminal Check: Inspect the connectors associated with fault P2 for moisture, scale buildup, loose pins, or heat discoloration.
- Digital Multimeter Verification: Unplug the suspect sensor or actuator and measure its resistance (Ω) or supply voltage against the nominal reference: NTC evaporator probe at 25°C: 10 kΩ (at -10°C: ~55 kΩ).
- Reassembly & Cycle Validation: Once the out-of-spec component is cleaned or replaced, restore power and execute the reset sequence.
4. How to Reset & Clear Dixell / Eliwell Error P2
🔄 Dixell / Eliwell P2 Reset: It is automatically cleared when replacing the evaporator probe.
🛠️ Compatible Replacement Parts & Tools
Need to replace the faulty component (NTC Temperature Sensor)?
Check OEM & aftermarket availability for Dixell NTC Temperature Sensor:
Want to use the interactive diagnostic wizard or electrical calculators for Dixell / Eliwell P2?
⚡ Open in Interactive Simulator →
⚡ Open in Interactive Simulator →
5. Frequently Asked Questions: Dixell / Eliwell Error Code P2
What does Dixell / Eliwell error code P2 mean?
Dixell / Eliwell P2: Failure in the evaporator defrost end probe (Equivalent to E2 in Eliwell) (Termostatos Digitales Cold Storage Rooms, Botelleros and Mesas Frías (XR20CX, XR60CX, ID974)). Multimeter Specs: NTC evaporator probe at 25°C: 10 kΩ (at -10°C: ~55 kΩ).
How do I reset Dixell / Eliwell fault code P2?
It is automatically cleared when replacing the evaporator probe.
What multimeter values should I check for Dixell / Eliwell code P2?
NTC evaporator probe at 25°C: 10 kΩ (at -10°C: ~55 kΩ)