Daikin · 10 Verified Diagnostic Sheets
ESENDEFRIT
Heat Pumps (Aerothermal)

Daikin Error Codes: Complete List (10 Faults), Causes & Reset

Complete technical directory of all 10 Daikin error codes (Heat Pumps (Aerothermal)) with exact meanings, multimeter reference specs, and reset instructions.

Error Code Technical Meaning Multimeter Specs
Daikin 7HProblem of insufficient water flow in the hydrokit (Error 7H-01)Minimum flow required at start-up: > 12 l/min (720 l/h)
Daikin A5Antifreeze protection (in cold) or high pressure control (in heat)Internal battery thermistor (R2T) at 25°C: 20 kΩ
Daikin A6Indoor unit fan motor blocked or faultyIndoor DC fan motor power supply: 310V DC (Red) / 15V DC (White)
Daikin AASupport heater safety thermostat tripped (Error AA-01)Backup Heater safety thermostat: Manual reset by physical button
Daikin E7Outdoor unit fan motor failureDC outdoor fan motor: 310V DC bus + 15V control
Daikin F3Compressor discharge pipe temperature excessively highDischarge thermistor (R3T) is 500 kΩ at 25°C (Different from 20 kΩ!)
Daikin L5Instantaneous overcurrent in the Inverter compressor (IPM Output)U-V, V-W, U-W compressor windings: 0.8 Ω to 2.5 Ω identical to each other
Daikin U0Low refrigerant gas pressure or lack of gasEEV expansion valve coil: ~46 Ω per phase | R32 cold pressure: ~8.5 bar
Daikin U3Slab drying cycle or incomplete initial configurationHydrokit hydraulic pressure: 1.5 - 2.0 bar
Daikin U4Communication failure between indoor and outdoor unitSignal terminals 2-3: 15V to 55V DC variable | External plate fuse: 3.15A
🛠️ Compatible Replacement Parts & Tools
Need to replace the faulty component (Replacement Sensor / Part)?

Check OEM & aftermarket availability for Daikin Replacement Sensor / Part: