| boilers 101 | overheat condition in el primary circuit of calefacción (> 100 °C): clean el Filter of malla of the tubo of retorno, desbloquear la Pump circuladora and purgar el Air | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers 103 | Circulación of Water insuficiente in el primary heat exchanger (Gradiente Thermal excesivo > 7 °C/s): Air in el circuito, Filter of retorno clogged / obstructed or Pump circuladora parada | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers 104 | flow rate insuficiente or diferencial excesivo (> 55 °C) between the NTC thermistor probe of ida and la NTC thermistor probe of retorno: Activar el ciclo of purgado Automatic manteniendo pulsado el Button of purge/casa | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers 108 | low water pressure fault in el circuito of calefacción (< 0.6 bar - Aviso 'filling insuficiente'): Abrir las llaves inferiores of filling until alcanzar 1.2 β 1.5 bar or puentear/replace el pressure switch hidráulico si está clogged / obstructed | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers 302 | Communication error GP-GI between the main control board (PCB) principal and la Board / Plate of interfaz of the panel frontal (Secar posible moisture in el panel frontal and inspect electrical connector of cinta) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers 501 | no flame detected (ignition lockout) al finalizar el ignition cycle (Boilers Ariston Genus / Clas One / Chaffoteaux): check and test Valve / Key of gas, inversión Fase-Neutro, sifón of condensados lleno or flame ionization electrode | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers 504 | Despegue or pérdida of Flame of the burner For / During el funcionamiento normal (3 veces in un ciclo): inspect recirculación of gases in el tubo coaxial of chimenea, sifón of condensados or calibración of CO2 | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers 601 | Intervención of the Probe / Sensor of tiro of chimenea (modelos atmosféricos) or Fault / Failure of latch / lock of the pressure switch neumático of evacuación of humos al arrancar el extractor (modelos estancos) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers A01 | El burner no se enciende after el ciclo of ignition (Boilers Ferroli Bluehelix / Domiproject / Cointra): check and test Valve / Key of gas, distancia of the electrodo (3.5 mm), sifón of condensados and Polarity Fase-Neutro | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers A02 | Signal of Flame presente with el burner off: Derivación Electric in el cable or cerámica of the flame ionization electrode or Fault / Failure in la tarjeta electrónica | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers A03 | Intervención of the protección contra overheat condition (> 90 °C): check and test que la Pump circuladora no esté blocked / jammed, purgar el Air of the intercambiador and inspect la Probe / Sensor doble of contacto/inmersión | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers A06 | no flame detected (ignition lockout) after la fase of ignition (La Flame se apaga 6 veces in 4 minutes): inspect pressure Minimum of gas, sifón of condensados clogged / obstructed and conducto of evacuación of humos | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers A7 | NTC thermistor probe of temperature of domestic hot water (DHW) (ACS) interrumpida or in short circuit (El Water sale templada or with cambios bruscos of temperature in Boilers Junkers) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers A8 | communication interrumpida in el bus of datos EMS with el Thermostat or programador ambiente modulante | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers B1 | El electrical connector codificador of modelo no es reconocido due to la main control board (PCB): Encajar bien la clavija codificadora gris in la Board / Plate or sustituirla | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers C4 | El pressure switch diferencial of humos does NOT open when the fan is at rest: Contactos of the pressure switch pegados or gotas of Water condensada dentro of los hoses / tubes of silicona of the Venturi | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers C6 | En Boilers of condensación Cerapur: El exhaust fan no gira or falla su Signal of revoluciones. in Boilers estancas atmosféricas: El pressure switch diferencial of humos no cierra al arrancar el extractor | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers CE | pressure of Water of the circuito of calefacción demasiado baja (< 0.6 bar): Rellenar Water desde la Valve / Key Lower until alcanzar 1.2 β 1.5 bar in frío | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E00 | Anomalía interna in la main control board (PCB) of control or open circuit in la NTC thermistor probe principal of impulsión | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E01 | Lockout / Blockage due to falta of ignition or no flame sensing circuit (Boilers Baxi / BaxiRoca / Ferroli): verify suministro of gas, clean flame ionization electrode and check and test que no se haya invertido Fase and Neutro in el power plug (girar clavija Schuko 180° and press Reset 2 seg) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E02 | Actuación of the high-limit safety thermostat due to overheat condition in el primary heat exchanger (> 95 °C): Desbloquear el eje of the Pump circuladora, purgar Air and press Reset | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E03 | Intervención of the pressure switch of seguridad of evacuación of humos or Thermostat of gases: Soplar los hoses / tubes of silicona of the Venturi, clean la turbina of the exhaust fan or replace el flue air pressure switch | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E04 | Lockout / Blockage of seguridad due to pérdida frecuente of Flame For / During el funcionamiento (6 desconexiones consecutivas): clean sifón of condensados and inspect tiro of chimenea and flame ionization electrode | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E05 | NTC thermistor probe of temperature of ida of calefacción abierta or in short circuit (En Boilers Baxi measure ~10 kΞ© a 25 °C) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E06 | NTC thermistor probe of the circuito of domestic hot water (DHW) (ACS) abierta or in short circuit | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E10 | El microinterruptor of the pressure switch hidráulico no cierra due to low water pressure fault (< 0.5 bar): Abrir la Valve / Key of filling azul/negra bajo la Boiler until 1.2β1.5 bar or clean la membrana of the pressure switch hidráulico | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E110 | Actuación of the Thermostat límite of seguridad or overheat condition of humos in Boilers of condensación Baxi Platinum / Neodens: check and test circulación of the Pump and purgado of Air | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E119 | Contacto of the pressure switch hidráulico open due to low water pressure fault (< 0.5 bar): Abrir la Valve / Key of filling until que el manómetro marque between 1.2 and 1.5 bar | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E125 | Seguridad due to falta of circulación of Water primaria or presencia of Air in la Boiler (temperature sube demasiado rápido: desbloquear Pump circuladora and clean Filter of retorno) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E133 | Fault / Failure due to falta of suministro of gas or no flame detected (ignition lockout) after agotarse los intentos of ignition (inspect Valve / Key of gas, sifón of condensados clogged / obstructed and flame ionization electrode in Baxi condensación) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E160 | Fault / Failure in el Fan of combustión: El Fan no alcanza el umbral of revoluciones consignado due to Fault / Failure in su Board / Plate integrada or Lockout / Blockage of the turbina | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E2 | NTC thermistor probe of temperature of ida of calefacción interrumpida or in short circuit (inspect electrical connector of the Probe / Sensor in el tubo of salida of the bloque Thermal) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E25 | Intervención of seguridad due to subida rápida of temperature (> 2 °C/seg): La Pump circuladora está agarrotada (quitar el tapón frontal and girar el eje with un destornillador) or hay Air atrapado in el intercambiador | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E35 | Flame parásita detectada with la gas solenoid valve cerrada: Derivación due to moisture in el flame ionization electrode or Fault / Failure in la main control board (PCB) (press Reset 2 seconds) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E9 | Se ha tripped el limitador of temperature (STB) of the bloque of calor or of gases of combustión due to overheating: check and test pressure of Water, purgar Air of the intercambiador and desbloquear el eje of the Pump circuladora | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers E96 | off Automatic due to voltage drop in la red Electric of Power supply (< 175V AC): La Boiler se reinicia sola when el voltaje of red se normaliza | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers EA | No se detecta Current of Ionization of Flame after el ignition (Boilers Junkers Cerapur / Cerastar / Bosch): check and test Valve / Key of gas abierta, limpieza of the sifón of condensados, flame ionization electrode desgastado and Polarity Fase-Neutro | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F0 | Fault / Failure interno in el Module electrónico of mando or conectores flojos in la main control board (PCB) principal | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F01 | open circuit or short circuit in la NTC thermistor probe of retorno of the primary circuit of calefacción (Saunier Duval ThemaFast / Thema Condens / IsoFast) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F02 | Fault / Failure in la NTC thermistor probe of temperature of domestic hot water (DHW) (ACS) or in el sensor of temperature of the acumulador Microfast (Saunier Duval) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F05 | Disparo of the high-limit safety thermostat of overheating (> 97 °C, press el botoncito central of the klixon to rearmar in modelos antiguos) or Fault / Failure of the pressure switch of evacuación of humos (Saunier Duval) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F09 | Avería Electric or taponamiento due to cal/lodo in el sensor captador of pressure hidráulica (Cp) of the circuito of calefacción (Saunier Duval Thema / IsoFast) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F11 | Ausencia of recepción of datos between el circuito electrónico principal and la tarjeta of visualización of the display frontal (inspect cable plano or Board / Plate principal Saunier Duval) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F13 | Fault / Failure interno in el microprocesador or memoria EEPROM of the main control board (PCB) principal of the Boiler (Apagar of the interruptor 1 minuto; si persiste, replace / change Board / Plate) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F14 | temperature of the Water of impulsión Upper a 95 °C: La Pump circuladora está blocked / jammed or el motor of the valve of 3 vías no abre el paso hacia el intercambiador | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F15 | Defecto in el mando of the motor paso a paso modulador of the bloque of gas (electrical connector suelto or bobinado of the motor of the gas solenoid valve cortado) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F2 | El limitador of temperature of seguridad (STB) ha actuado due to overheating in Boiler Viessmann Vitodens: inspect level of filling of the instalación, desbloquear heating circulation pump and purgar Air | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F20 | off of seguridad due to el limitador of overheat condition (STB > 95 °C): El calor no se disipa of the primary heat exchanger porque la Pump circuladora está blocked / jammed, las llaves of radiadores cerradas or hay Air | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F22 | Funcionamiento in seco or low water pressure fault in el circuito of calefacción (< 0.5 bar): Abrir la Valve / Key of filling Lower until situar la pressure between 1.2 and 1.5 bar or replace el sensor of pressure si marca 0.0 bar with Water | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F27 | Simulación of Flame / Flame parásita detectada with el burner off: moisture or derivación a masa in la cerámica of the flame ionization electrode or Fault / Failure in el circuito detector of Flame of the Board / Plate | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F28 | Lockout / Blockage in el ignition (sin Flame): check and test suministro of gas open, flame ionization electrode cubierto of óxido blanco, sifón of condensados clogged / obstructed or gas solenoid valve blocked / jammed (Vaillant ecoTEC / Saunier Duval) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F29 | Pérdida of Flame For / During el funcionamiento and reencendido fallido: inspect Drain of the sifón of condensados jammed / stuck (inunda la cámara of combustión), junta of the tubo coaxial of humos suelta or corte intermitente of gas | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F32 | Velocidad of giro of the Fan fuera of tolerancia: exhaust fan jammed / locked due to suciedad, electrical connector Hall PWM suelto or main control board (PCB) integrada in el motor of the Fan quemada | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F37 | pressure of Water of the instalación insuficiente (< 0.8 bar): Abrir la Valve / Key of filling Lower until situar el manómetro in 1.2 β 1.5 bar; si persiste with pressure, clean or replace el pressure switch hidráulico | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F4 | burner in avería (sin Signal of Flame in Boilers of condensación Viessmann Vitodens 050-W / 100-W / 200-W): check and test Valve / Key of gas, distancia and limpieza of the flame ionization electrode, sifón of condensados and relé of gas solenoid valve | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F43 | Intervención of the protección of the intercambiador due to velocidad of calentamiento excesiva: Falta of flow rate of Water due to Air in el intercambiador, Pump blocked / jammed or intercambiador calcificado | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F49 | Detección of subtensión or short circuit in la línea of communication of dos hilos eBUS hacia el Thermostat or Module solar | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F54 | Falta of pressure of entrada of gas natural / GLP or activación of the pressure switch of Minimum pressure of gas | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F61 | Fault / Failure in el mando of control of the gas solenoid valve: short circuit in el wiring harness of the gas solenoid valve, coil of the motor paso a paso averiada or relé/driver faulty in la main control board (PCB) principal | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F62 | Retardo excesivo in la desconexión of the gas solenoid valve or flame sensing circuit after el latch / lock: gas solenoid valve que no cierra herméticamente or avería interna in la main control board (PCB) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F7 | Se detecta una Signal of Flame falsa aunque el burner está off: Secar moisture in torno al flame ionization electrode and cable of bujía or replace Board / Plate | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F72 | Incoherencia permanente of temperature between the NTC thermistor probe of ida and la NTC thermistor probe of retorno of the primary heat exchanger (replace el par of NTC sensors of contacto/inmersión) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F73 | Signal of the sensor of pressure of Water demasiado baja (short circuit a masa or electrical connector of 3 pines desconectado of the transductor hidráulico) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F74 | Signal of the sensor of pressure of Water demasiado alta: short circuit a +5V in el sensor or sobrepresión real > 4.0 bar due to Valve / Key of filling abierta | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F75 | No se detecta salto of pressure (+50 mbar) al arrancar la Pump circuladora: Orificio of the sensor of pressure of Water clogged / obstructed due to lodo negro of radiadores, expansion vessel without Air or rotor of the Pump jammed / locked (Vaillant ecoTEC) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers F83 | Incremento of temperature insuficiente in las NTC sensors after encender el burner: Presencia of Air in el primary heat exchanger, falta of Water or NTC sensors desacopladas of the tubo | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers FA | Detección of Current of Ionization (Flame presente) after desconectarse la gas solenoid valve: La gas solenoid valve no cierra el paso due to completo or hay Fault / Failure in la main control board (PCB) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers FD | key / button of rearme (Reset) pulsada due to error For / During más of 30 seconds consecutivos: Volver a press el Button Reset una sola vez For / During 2 seconds to desbloquear | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers H01 | flow rate of Water insuficiente in el circuito hidráulico of the Pump of calor of Aerotermia (Error of Flow Switch): clean el Filter of malla metálica (Filter in Y) in el retorno of calefacción, abrir circuitos of suelo radiante and purgar Air | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |
| boilers SP1 | Primer or segundo ignition attempt without flame sensing circuit (Aviso transitorio SP1 / 5P1 / 5P3 antes of entrar in Lockout / Blockage definitivo 501; inspect flame ionization electrode and sifón) | Power supply nominal: 230V AC ±10% / Comprobación of continuidad and insulation with multímetro digital |