Mitsubishi Electric · 6 Verified Diagnostic Sheets
ESENDEFRIT
Air Conditioning

Mitsubishi Electric Error Codes: Complete List (6 Faults), Causes & Reset

Complete technical directory of all 6 Mitsubishi Electric error codes (Air Conditioning) with exact meanings, multimeter reference specs, and reset instructions.

Error Code Technical Meaning Multimeter Specs
Mitsubishi Electric E6Indoor/outdoor serial communication failure (6 flashes)S1-S2 voltage: 230V AC | S2-S3 signal: 12V-24V DC pulsating
Mitsubishi Electric L9Low flow rate in the primary water circuit (Error L9)Ecodan minimum flow rate: > 10 - 15 l/min depending on model
Mitsubishi Electric P2Defective inner liquid pipe probe (2 flashes)Resistance TH2 at 25°C: 10 kΩ
Mitsubishi Electric P5Condensate overflow / Drain pump failure (5 flashes)Level buoy (CN4F): Closed (0 Ω) at normal level, Open with full water
Mitsubishi Electric P8Abnormal pipe temperature (8 LED flashes)Inner pipe probe (TH2) at 25°C: 10 kΩ
Mitsubishi Electric U3Compressor discharge thermistor open or shorted (TH4)Discharge thermistor TH4 at 25°C: 250 kΩ (at 70°C: 34 kΩ)