GoodWe / Growatt Error Code Isolation Fault: Meaning, Multimeter Diagnosis & Fix
1. Technical Specifications & Multimeter Values (GoodWe / Growatt Isolation Fault)
| Manufacturer / Brand | GoodWe / Growatt |
|---|---|
| Error Code | Isolation Fault |
| System / Category | Solar Inverters & Water Heaters |
| Compatible Models | Solar Inverters GW3000-6000D-NS, EH, ET, Growatt MIN / SPH |
| Severity Level | High Severity · Safety Lockout |
| Multimeter Specs | DC+ to Ground and DC- to Ground insulation: > 1 MΩ |
2. Guided Symptom Troubleshooting Matrix
Some MC4 connector on the roof has water in it or a solar cable rubs against the aluminum structure, lowering the ground resistance from the minimum 200 kΩ. Disconnect String 1 and try only String 2 (and vice versa) to find out which series of panels the branch is on.
DC surge varistor in the grounded protection panel.
3. Step-by-Step Multimeter Testing Procedure (Isolation Fault)
- Safety Power Isolation: Disconnect the GoodWe / Growatt unit from mains power (230V / 120V AC) and wait at least 3 minutes for PCB capacitors to discharge before opening panels.
- PCB & Harness Terminal Check: Inspect the connectors associated with fault Isolation Fault for moisture, scale buildup, loose pins, or heat discoloration.
- Digital Multimeter Verification: Unplug the suspect sensor or actuator and measure its resistance (Ω) or supply voltage against the nominal reference: DC+ to Ground and DC- to Ground insulation: > 1 MΩ.
- Reassembly & Cycle Validation: Once the out-of-spec component is cleaned or replaced, restore power and execute the reset sequence.
4. How to Reset & Clear GoodWe / Growatt Error Isolation Fault
Check OEM & aftermarket availability for GoodWe Replacement Sensor / Part:
⚡ Open in Interactive Simulator →
5. Frequently Asked Questions: GoodWe / Growatt Error Code Isolation Fault
What does GoodWe / Growatt error code Isolation Fault mean?
GoodWe / Growatt Isolation Fault: Low insulation resistance of solar panels with respect to ground (Fac Error / Isolation Failure) (Solar Inverters GW3000-6000D-NS, EH, ET, Growatt MIN / SPH). Multimeter Specs: DC+ to Ground and DC- to Ground insulation: > 1 MΩ.
How do I reset GoodWe / Growatt fault code Isolation Fault?
Identify the tapped string by disconnecting them alternately at the DC disconnector (no load) and change the wet MC4 connector.
What multimeter values should I check for GoodWe / Growatt code Isolation Fault?
DC+ to Ground and DC- to Ground insulation: > 1 MΩ